NSN 5925-00-279-6733 Repair Services

Circuit Breaker Overhaul, Repair, and Maintenance

MPN: ALB5, MILC17588TYPEALB5

Pricing and Lead Time Quote

Submit this form and receive an overhaul/repair pricing and lead time quote for NSN 5925-00-279-6733 circuit breaker
Your Email:
Your Name:
Company Name:
Optional reference:
Phone:
NSN 5925002796733


Privacy | Terms

AS9120B:2015 ISO 9001 Audited and Certified

FAA and EASA Part 145 Certified Repair Stations Ensuring the highest standards of quality and compliance for our clients' needs.

We specialize in the repair and refurbishment of nsn components. From mechanical assemblies to rotor blades, our comprehensive capabilities cover a wide range of NSN parts, providing cost effective solutions to extend the operational life of vital equipment.

NSN 5925-00-279-6733 has been designated as a repairable item and has been included in our capabilities catalog. If you require overhaul or repair services use the form on this page to send us your information. We will provide you with a lead time and price quote.

Repairability and Datasheet

NSN 5925-00-279-6733 can be offered in repaired, serviceable, overhauled, or inspected conditions.
National Stock Number (NSN) 5925-00-279-6733
Categorization Automatic circuit breakers, for a voltage not exceeding 1,000 v
Repairability Code

Approximate Weight 0.0lb
Overall Length 4.125 inches
Overall Height 4.125 inches
Overall Width 3.344 inches
Case Material Plastic
Pole Quantity 3
Arc Quenching Method Air
Maximum Continuous Load Current Rating Per Pole 25.0 amperes ac all locations and 25.0 amperes dc all locations
Operating Voltage Type And Rating Per Pole In Volts 120.0 ac all locations and 120.0 dc all locations
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps 5000.0 ac all locations and 5000.0 dc all locations
Circuit Protection Type Overcurrent all locations
Trip Release Method Magnetic all locations
Trip Release Characteristic Instantaneous all locations and time delay all locations
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent 115.0 all locations
Reset Method Manual
Main Contact Tripping Mechanism Type Trip free
Manual Actuator Type And Quantity 1 toggle
Actuator Function Reset
Trip Delay Time In Seconds Per Rated Continuous Current 10.000 at 200 pct all locations and 100.000 at 200 pct all locations
Inclosure Protection Type For Which Designed Shockproof
Trip Release Ambient Tempurature Rating 50.0 degrees celsius all locations
Frequency In Hertz 60.0 all locations
Terminal Type And Quantity 6 pin

Part Numbers

Part Number Company RNAAC (Repair Depot)
ALB5 MILITARY SPECIFICATIONS XX -
MILC17588TYPEALB5 MILITARY SPECIFICATIONS XX -