NSN 5925-00-175-5237 Repair Services
Circuit Breaker Overhaul, Repair, and Maintenance
MPN: 29478, AT21050, P7767053P10
Pricing and Lead Time Quote
Submit this form and receive an overhaul/repair pricing and lead time quote for NSN 5925-00-175-5237 circuit breakerFAA and EASA Part 145 Certified Repair Stations Ensuring the highest standards of quality and compliance for our clients' needs.
We specialize in the repair and refurbishment of nsn components. From mechanical assemblies to rotor blades, our comprehensive capabilities cover a wide range of NSN parts, providing cost effective solutions to extend the operational life of vital equipment.
NSN 5925-00-175-5237 has been designated as a repairable item and has been included in our capabilities catalog. If you require overhaul or repair services use the form on this page to send us your information. We will provide you with a lead time and price quote.
Repairability and Datasheet
NSN 5925-00-175-5237 can be offered in repaired, serviceable, overhauled, or inspected conditions.National Stock Number (NSN) | 5925-00-175-5237 |
Categorization | Automatic circuit breakers, for a voltage not exceeding 1,000 v |
Repairability Code | |
Approximate Weight | 0.0lb |
Case Material | Plastic |
Unthreaded Mounting Hole Diameter | 0.188 inches |
Pole Quantity | 2 |
Mounting Facility Type And Quantity | 4 unthreaded hole |
Maximum Continuous Load Current Rating Per Pole | 50.0 amperes ac all locations and 50.0 amperes dc all locations |
Operating Voltage Type And Rating Per Pole In Volts | 240.0 ac all locations and 240.0 dc all locations |
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 5000.0 ac all locations and 5000.0 dc all locations |
Circuit Protection Type | Overcurrent all locations |
Trip Release Method | Thermal all locations |
Trip Release Characteristic | Time delay all locations |
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 122.0 all locations |
Reset Method | Manual |
Main Contact Tripping Mechanism Type | Trip free |
Internal Trip Release Configuration | Series trip all locations |
Trip Delay Time In Seconds Per Rated Continuous Current | 18.000 at 200 pct all locations and 105.000 at 200 pct all locations |
Trip Release Ambient Tempurature Rating | 25.0 degrees celsius all locations |
Terminal Type And Quantity | 4 threaded stud |
Part Numbers
Part Number | Company | RNAAC (Repair Depot) |
---|---|---|
29478 | NAVAL SHIP SYSTEMS COMMAND | TX - DLA LAND AND MARITIME |
AT21050 | GENERAL ELECTRIC CO | TX - DLA LAND AND MARITIME |
P7767053P10 | GENERAL ELECTRIC CO | TX - DLA LAND AND MARITIME |